PM8240 multifunction network analyser – Ethernet – Class 0.2S – panel mount meter

Short description

PM8240 multifunction network analyser – Ethernet – Class 0.2S – panel mount meter

Brand
Schneider Electric
Product name
PowerLogic PM8000
Accuracy class [Ea]
Class 0.2S
Best for
New installation
Communication
DNP3
IEC 61850
ION
Modbus RS485
Modbus TCP/IP
Modbus TCP/IP
Current measurement method
External CT 1A/5A
Current measurement range
50...10000 mA
Device application
WAGES metering
Power monitoring
MID compliant
No
Mounting mode
Panel/door
Multi-tariff
No
Number of digital inputs
6
Number of digital outputs
1
Poles description
1P + N
3P
3P + N
Power quality data
Yes (Advanced)
Rated current [In]
1 A (CT input)
5 A (CT input)
10 A (CT input)
Type of measurement
Active power per phase, rms
Reactive power per phase, rms
Active power total
Reactive power total
Power factor
Power factor per phase, rms
Frequency
Voltage
Apparent power per phase, rms
Apparent power total
THD (U) per phase
THD (I) per phase
Current

10+ pieces available in 6-8 days

2.218,00  excl. VAT
Price Range
Amount (pcs)Price
1+2,218.00 €
5+2,180.00 €
10+2,143.00 €

Description

The PowerLogic PM8000 series meters are compact, cost-effective multifunction power meters that will help you ensure reliability and efficiency of your power-critical facility. They reveal and provide understanding of complex power quality conditions enabling action to be taken to mitigate any issue. The PowerLogic PM8000 series meters are versatile enough to execute practically any task a meter is required to perform, in any environment! The modular, flexible ION technology architecture enables a simple, building block approach for customizing each meter to any application. It can detect the source of the power quality event. Recommended to be used with EcoStruxure Power Monitoring Expert software from Schneider Electric. With patented Disturbance Direction Detection, revenue grade accuracy, multiple communication ports, onboard power quality analysis, web interface and a color graphical display. Certified by third party labs for energy accuracy (IEC 62052-11, IEC 62052-22, IEC 62052-24) and power quality (IEC 62586-2, IEC 61000-4-30 Class S). The PowerLogic PM8000 series provides data quality confidence you can count on. Cybersecurity features include secure protocols (HTTPS, SFTP), security event logging, Syslog protocol. Ability to enable/disable communication ports, and 50 user configurable accounts. With 512 MB of memory to support 50 data logs, 50+ user-definable alarms, waveform captures, 1/2 cycle RMS logging, custom web pages, min/max logs, energy trends, and Time of Use. The ability to timestamp events to +/-1 ms utilizing time synchronization method that include PTP (IEEE1588), NTP, IRIG-B, GPS ASCII (RS485) and network time set function. 3 digital inputs and one digital output, plus the ability to add up to 4 option modules. I/O option modules include 2 relays and 6 digital inputs or 2 analog outputs and 4 analog inputs. Wide control power range of 90-415 VAC / 110-415 VDC. Operating environment of -25 to +70C; Humidity rating of 5% to 95%; Altitude up to 3000 m. Panel mounting (1/4 DIN) with integrated display. It assists in actively ensuring that the electrical system operates constantly and as efficiently as possible. You can: boost your industrial facility’s efficiency, cut back on production losses and reduce maintenance expenditures and optimize operating costs.

Specifications

Main
Accuracy class
Class 0.2 active energy conforming to ANSI C12.20
Class 0.2 active power conforming to IEC 61557-12
Class 0.2 voltage conforming to IEC 61557-12
Class 0.2 current conforming to IEC 61557-12
Class 0.2S active energy conforming to IEC 62053-22
Class 0.5 power factor conforming to IEC 61557-12
Class 0.5S reactive energy conforming to IEC 62053-24
Device short name
PM8240
Measurement accuracy
Active energy +/- 0.2 %
Voltage +/- 0.1 %
Current +/- 0.1 %
Power quality analysis
Up to the 63rd harmonic
Power factor (PF)
Voltage sag and swell detection
Programmablity (logic and math functions)
Total harmonic distortion (THD)
Conforming to EN 50160: 2010 compliance report
Conforming to IEC 61000-4-30: class S power quality measurement
Conforming to IEC 62586 power quality monitoring
Conforming to IEEE 519: 2014 compliance report
Waveform capture
Product or component type
Power Quality Analyzer
Range of product
PowerLogic
Rated supply voltage [Us]
110...415 V DC +/- 10 %
90...415 V AC 45...65 Hz +/- 10 %
Type of measurement
Active power per phase, rms
Reactive power per phase, rms
Active power total
Reactive power total
Power factor
Power factor per phase, rms
Frequency
Voltage
Apparent power per phase, rms
Apparent power total
THD (U) per phase
THD (I) per phase
Current
Complementary
Communication port protocol
DNP3
Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s
IEC 61850
ION at 115 kbauds - 2-wire
Modbus RTU at 115 kbauds - 2-wire
Modbus TCP/IP
RSTP 801.1d 2004
Communication port support
Ethernet
RS485
Data recording
Time stamping
GPS synchronisation
Min/max of instantaneous values
Trending/forecasting
Alarm logs
Event logs
Harmonics logs
Data logs
Sag and swell logs
Waveform logs
Sequence of event recording
Complementary Depth
77.5 mm
Display resolution
320 x 240 pixels QVGA
Display type
Colour TFT LCD
Frequency measurement range
42...69 Hz
Complementary Height
96 mm
Information displayed
Frequency
Harmonic distortion
Power
Voltage
Energy consumption
Current
Input impedance
Voltage (impedance 5 MOhm)
Current (impedance 0.3 mOhm)
Memory capacity
512 MB
Net weight
581 g
Network frequency
50 Hz
60 Hz
Number of inputs
3 digital 30 V AC
3 digital 60 V DC
Number of outputs
1 pulse
Sampling rate
256 samples/cycle
Standards
IEC 61326-1
IEC 61557-12
IEC 62052-11
IEC 62053-22
IEC 62053-24
IEC 62586-2
IEEE 1588
Target application
Utility: sub feeder
Industry network management: main incomer
Industry network management: sub feeder
Buildings small building network management: main incomer
Data center network management: main incomer
Data center network management: sub feeder
Buildings medium building network management: main incomer
Buildings multi-site network management: main incomer
Buildings multi-site network management: sub feeder
Buildings large building network management: main incomer
Buildings large building network management: sub feeder
Buildings large building cost management: billing: sub feeder
Healthcare network management: main incomer
Healthcare network management: sub feeder
Type of measurement
Active power per phase, rms
Reactive power per phase, rms
Active power total
Reactive power total
Power factor
Power factor per phase, rms
Frequency
Voltage
Apparent power per phase, rms
Apparent power total
THD (U) per phase
THD (I) per phase
Current
Voltage measurement range
100-690 V AC 42...69 Hz between phases
57-400 V AC 42...69 Hz between phase and neutral
Web services
HTTPS server
Alarm notification by e-mail
Viewing of captured waveform (FTP)
Viewing of captured waveform (web)
File upload/download via FTP
File upload/download via SFTP
Customizable home page
Web server
Complementary Width
96 mm
Enviroment
Ambient air temperature for operation
-25...70 °C
Ambient air temperature for storage
-40...85 °C
Electromagnetic compatibility
Electrostatic discharge conforming to IEC 61000-4-2
Immunity to impulse waves conforming to IEC 61000-4-12
Electrical fast transient/burst immunity test conforming to IEC 61000-4-4
Surge immunity test conforming to IEC 61000-4-5
Surge withstand conforming to IEEE C37.90.1
Magnetic field at power frequency conforming to IEC 61000-4-8
Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
Conducted and radiated emissions conforming to EN 55011
Conducted and radiated emissions conforming to EN 55022
Conducted and radiated emissions conforming to FCC part 15
Conducted and radiated emissions conforming to ICES-003
Conducted RF disturbances (2...150 Hz) conforming to CLC/TR 50579
Conducted RF disturbances conforming to IEC 61000-4-6
Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
IP degree of protection
IP30 body: conforming to IEC 60529
IP54 front: conforming to IEC 60529
Net weight
581 g
Operating altitude
< 3000 m
Relative humidity
5...95 %
Standards
IEC 61326-1
IEC 61557-12
IEC 62052-11
IEC 62053-22
IEC 62053-24
IEC 62586-2
IEEE 1588