iEM2435 direct single phase energy meter – 230V – 100A – M-bus

Short description

iEM2435 direct single phase energy meter – 230V – 100A – M-bus

Brand
Schneider Electric
Product name
Acti 9 iEM2000
Accuracy class [Ea]
Class 1
Best for
New installation
Communication
M-bus
Current measurement method
Direct input
Current measurement range
5…100 A
Device application
Sub billing
Multi-tariff
MID compliant
Yes
Mounting mode
DIN rail
Multi-tariff
Yes
Poles description
1P + N
Power quality data
Yes (PF only)
Rated current [In]
100 A
Type of measurement
Active energy
Reactive energy
Active power
Reactive power
apparent power
power factor
current
voltage
frequency

10+ pieces available in 13-15 days

83,00  excl. VAT
Price Range
Amount (pcs)Price
1+83.00 €
5+81.00 €
10+80.00 €

Description

The energy meters in the Acti9 iEM2435 series are DIN rail-mounted, single-phase energy meters designed for simple metering. This product series is useful for managing electrical installations for building management as well as monitoring power consumption for each sector, unit, or workshop. It has a red LED indication to show measured electrical characteristics, along with a display with seven characters or digits. The meter will measure Active and Reactive Power, Active and Reactive Energy, Voltage, and Current with Class 1 active energy accuracy in accordance with IEC 62053-21 standard. With a supply voltage range of 96 to 276 VAC at 50Hz or 60Hz, it is appropriate for a 230VAC network. Direct connect current measurement in single phase and neutral setup up to 100A with only 32 samples per cycle. There are no extra communication ports; M-Bus is the communication protocol, and 2-wire terminals are supported. It will be possible for you to move between two tariffs using the communication bus. The product has the following measurements: height 96.71 mm, width 35.8 mm, depth 63 mm, and weight 220 g. This version complies with the Measuring Instruments Directive (MID) standard EN 50470-3 class B. able to benefit from the Internet of Things digital power installation when combined with power management software.

Specifications

Main
Accuracy class
Class 1 active energy conforming to IEC 62053-21
Class 2 reactive energy conforming to IEC 62053-23
Class B active energy conforming to EN 50470-3
Device short name
iEM2435
Power quality analysis
Power factor (PF)
Product or component type
Energy meter
Range of product
PowerLogic
Type of measurement
Active energy
Reactive energy
Active power
Reactive power
apparent power
power factor
current
voltage
frequency
Complementary
9 mm pitches on DIN rail
4
Colour
White (RAL 9003)
Communication port protocol
M-bus at 300, 600, 1200, 2400, 4800 and 9600 bauds - 2 wires, insulation 3750 V
Communication port support
screw terminals: M-Bus
Complementary Depth
63 mm
Display type
LCD display
Complementary Height
96.7 mm
Impulse duration
5...32 ms
Information displayed
Tariff (2)
Local signalling
red LED: metering and activity 0.01, 0.1, 1, 10, 100, 1000, 2000 or 10000 p/kWh
Maximum power consumption in VA
1 VA at 240 V AC
Network frequency
50 Hz
60 Hz
Standards
IEC 62052-11
IEC 62053-21
IEC 61010-1
Target application
buildings small building cost management: billing: panelboard
buildings medium building cost management: billing: panelboard
buildings large building cost management: billing: panelboard
buildings multi-site cost management: billing: panelboard
data center cost management: billing: panelboard
healthcare cost management: billing: panelboard
industry cost management: billing: panelboard
buildings small building cost management: cost allocation: panelboard
buildings medium building cost management: cost allocation: panelboard
buildings large building cost management: cost allocation: panelboard
buildings multi-site cost management: cost allocation: panelboard
data center cost management: cost allocation: panelboard
healthcare cost management: cost allocation: panelboard
industry cost management: cost allocation: panelboard
Type of measurement
Active energy
Reactive energy
Active power
Reactive power
apparent power
power factor
current
voltage
frequency
Complementary Width
35.8 mm
Enviroment
Ambient air temperature for operation
-25...55 °C
Ambient air temperature for storage
-30...70 °C
IP degree of protection
IP51 front panel: conforming to IEC 60529
IP20 casing:
Operating altitude
< 2000 m
Relative humidity
0...95 %
Standards
IEC 62052-11
IEC 62053-21
IEC 61010-1