DM6000H Panel instrument – Basic parameters (V,A,f) – LCD – Class 1 (U,I)

ID: METSEDM6000HCL10NC

Short description

DM6000H Panel instrument – Basic parameters (V,A,f) – LCD – Class 1 (U,I)

Brand
Schneider Electric
Accuracy class [Ea]
Class 1
Best for
New installation
Communication
Without
Current measurement method
External CT 1A/5A
Current measurement range
5...6000 mA
Device application
Monitoring
Mounting mode
Panel/door
Multi-tariff
No
Poles description
2P + N
2P
3P + N
3P
1P + N
Rated current [In]
1 A (CT input)
5 A (CT input)
Type of measurement
current
voltage
frequency
RPM

10+ pieces available in 6-8 days

74,00  excl. VAT
Price Range
Amount (pcs)Price
1+74.00 €
5+72.00 €
10+71.00 €

Description

A member of the EasyLogic Digital Panel Meter Series is this digital panel meter. With the use of a multicolored bar, the device can analyze the load and display the present burden. According to IEC 62053-21 standard, the meter will measure voltage, current, and power factor with Class 1 accuracy. The meter is 15 mm tall, contains four numbers, eight segments, and a brilliant red LED display. The product’s mechanical measurements are 80 mm in depth, 96 mm in width, and 96 mm in height. It weighs 400 g.

Specifications

Main
Accuracy class
Class 1
Device short name
DM6000H
Measurement accuracy
frequency +/- 0.05 %
power factor +/- 0.01
current +/- 1 %
voltage +/- 1 %
Product or component type
Panel instrument
Range of product
EasyLogic
Type of measurement
current
voltage
frequency
RPM
Complementary
Complementary Depth
13 mm outside:
49 mm panel
Display type
8 segments LED
Frequency measurement range
45...65 Hz
Complementary Height
96 mm
Local signalling
green LED: activity
red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh)
Maximum power consumption in VA
4 VA at 240 V AC
Maximum power consumption in W
2 W at 240 V
Net weight
300 g
Network frequency
50 Hz
60 Hz
Standards
IEC 61010-1:ed. 3
UL 61010-1:ed. 3
Type of measurement
current
voltage
frequency
RPM
Voltage measurement range
35-480 V AC 50...60 Hz between phases
46-277 V AC 50...60 Hz between phase and neutral
277-999000 V AC 50...60 Hz with external VT
Complementary Width
96 mm
Wire stripping length
current circuit: 3.68 mm
voltage circuit: 7 mm
control circuit: 7 mm
Enviroment
Ambient air temperature for operation
-10...60 °C
Ambient air temperature for storage
-20...70 °C
Electromagnetic compatibility
Electrostatic discharge conforming to IEC 61000-4-2
radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3
electrical fast transient/burst immunity test conforming to IEC 61000-4-4
surge immunity test conforming to IEC 61000-4-5
conducted RF disturbances conforming to IEC 61000-4-6
magnetic field at power frequency conforming to IEC 61000-4-8
voltage dips and interruptions immunity test conforming to IEC 61000-4-11
emission tests conforming to FCC part 15 class A
emission tests conforming to FCC part 15 Subpart C
emission tests conforming to FCC part 15 Subpart E
IP degree of protection
IP51 front: conforming to IEC 60529
IP30 body: conforming to IEC 60529
Net weight
300 g
Operating altitude
<= 2000 m
Overvoltage category
III
Relative humidity
5...95 % at 50...50 °C
Standards
IEC 61010-1:ed. 3