Energy sensor PowerTag Rope 600A 3P/3P+N top or bottom position of the breaker or switch

Short description

Energy sensor PowerTag Rope 600A 3P/3P+N top or bottom position of the breaker or switch

Brand
Schneider Electric
Product name
PowerTag
Accuracy class [Ea]
Class 1
Best for
Switchboard upgrade
Communication
Modbus TCP/IP
Concentrator compatibility
EcoStruxure Panel Server Entry PAS400
EcoStruxure Panel Server Universal (PAS600L/PAS600T)
EcoStruxure Panel Server Universal (PAS800/PAS800L/PAS800P)
PrismaSet Active
Current measurement method
Direct input
Current measurement range
0…600 A
Device application
Overload alarm
Breaker voltage monitoring
Sub billing
Diameter
Closed: 100 mm
MID compliant
No
Mounting mode
DIN rail
Multi-tariff
No
Poles description
3P
3P + N
Power quality data
Yes (PF only)
Rated current [In]
600 A
Type of measurement
Active energy
Reactive energy
Active power
Reactive power
Power factor
Frequency
Voltage
Apparent energy
Apparent power
Internal temperature
Current

10+ pieces available in 6-8 days

534,00  excl. VAT
Price Range
Amount (pcs)Price
1+534.00 €
5+525.00 €
10+516.00 €

Description

PowerLogic PowerTag Energy R600 3P/3P+N is a wireless communication energy sensor. With its Rope design, It is intended for 3P and 3P+N networks rating up to 600A. This Rope verison of PowerTag is 100% compatible with any other producers like ABB, SIEMENS, EATON, Legrand, Schrack, ETI etc. as it can be placed on cables or any copper and aluminium busbars. It has to be associated with a concentrator or a gateway to provide circuit monitoring and diagnosis down to load level. It is made especially for Energy Management, Energy Efficiency, Load Monitoring and Power Availability applications. It incorporates accurate real-time measurements of active, reactive and apparent energy, active, reactive and apparent power, current, voltage and power factor. In case of power outage, it sends a voltage loss alarm and the current-per-phase value before being de-energized. PowerTag Energy R600 complies with IEC 61557-12 standard. It is a PMD-II/DD/K70/1. Class performance fits under Class 1. The Imax maximum current is 600A. The Ib Base current is 100A. The Saturation current is 1200A and the Ist Starting current is 400mA. The Un Rated voltages are Phase-to-neutral 100 to 277VAC +/- 20% and Phase-to-phase 173 to 480VAC +/- 20%. The maximum consumption is below or equal to 3VA. It can be either mounted on bare or insulated busbars or on cables. The product color is white (RAL9003). The weight is 360g. The degree of protection is IP20 (IP40 front face) and IK05. The operating temperature is between -25°C to +70°C. The storage temperature is between -40°C to +85°C.

Specifications

Main
Accuracy class
Class 0.5 frequency conforming to IEC 61557-12
Class 0.5 voltage conforming to IEC 61557-12
Class 1 active energy conforming to IEC 61557-12
Class 1 active power conforming to IEC 61557-12
Class 1 power factor conforming to IEC 61557-12
Class 1 current conforming to IEC 61557-12
Class 2 reactive energy conforming to IEC 61557-12
Class 2 reactive power conforming to IEC 61557-12
Class 2 apparent energy conforming to IEC 61557-12
Class 2 apparent power conforming to IEC 61557-12
Basic current [Ib]
100A
Device short name
PowerTag
Mounting location
Top or bottom
Mounting support
Cables
Busbar
Power quality analysis
Power factor (PF)
Product or component type
Energy meter
Range compatibility
Acti9
ComPact NS
Masterpact MTZ switch disconnector
MasterPact NT
Masterpact NW
TeSys
Range of product
PowerLogic
Saturation current
1200 A
Starting current
400 mA
Type of measurement
Active energy
Reactive energy
Active power
Reactive power
Power factor
Frequency
Voltage
Apparent energy
Apparent power
Internal temperature
Current
Complementary
9 mm pitches on DIN rail
2
Cable cross section
1 stranded cable 0.2-2.5 mm² without cable end
1 stranded cable 0.25-1.5 mm² with cable end
1 rigid cable 0.2-1.5 mm² without cable end
Cable length
1 m for sensor
Colour
White (RAL 9003)
Communication port protocol
Modbus TCP/IP (concentrator)
Communication port support
Ethernet (concentrator)
Complementary Depth
Base unit: 67.5 mm
Complementary Height
Base unit: 105 mm
Mounting support
Cables
Busbar
Network frequency
50 Hz
60 Hz
Rated insulation voltage [Ui]
100...277 V AC, +/- 20 %, phase to neutral
173...480 V AC, +/- 20 %, phase to phase
Standards
ETSI EN 301 487-1
IEC 61010
IEC 61557-12
Transmission support medium
Radio frequency 2.4-2.4835 GHz conforming to IEEE 802.15.4
Type of measurement
Active energy
Reactive energy
Active power
Reactive power
Power factor
Frequency
Voltage
Apparent energy
Apparent power
Internal temperature
Current
Complementary Width
Base unit: 18 mm
Wire stripping length
11 mm
Enviroment
Ambient air temperature for operation
-25...70 °C
Ambient air temperature for storage
-40...85 °C
Directives
2014/53/EU - radio equipment directive
Electromagnetic compatibility
Electromagnetic emission conforming to IEC 62311
Industrial electromagnetic environment conforming to IEC 61326-1
Radiated EMC conforming to ETSI EN 301 489-17
Environmental characteristic
Indoor use
IK degree of protection
IK05
IP degree of protection
IP20 conforming to IEC 60529
Operating altitude
< 2000 m
Overvoltage category
IV conforming to IEC 61010-1
Relative humidity
0...95 % at 55 °C conforming to IEC 60721-3-3
Standards
ETSI EN 301 487-1
IEC 61010